1 | AN ACT concerning safety.
| ||||||||||||||||||||||||
2 | Be it enacted by the People of the State of Illinois,
| ||||||||||||||||||||||||
3 | represented in the General Assembly:
| ||||||||||||||||||||||||
4 | Section 5. The Smoke Detector Act is amended by changing | ||||||||||||||||||||||||
5 | Section 3 as follows:
| ||||||||||||||||||||||||
6 | (425 ILCS 60/3) (from Ch. 127 1/2, par. 803)
| ||||||||||||||||||||||||
7 | Sec. 3.
(a) Every dwelling unit or hotel shall be equipped | ||||||||||||||||||||||||
8 | with at least one
approved smoke detector in an operating | ||||||||||||||||||||||||
9 | condition within 15 feet of every room
used for sleeping | ||||||||||||||||||||||||
10 | purposes. The detector shall be installed on the ceiling
and at | ||||||||||||||||||||||||
11 | least 6 inches from any wall, or on a wall located between 4 | ||||||||||||||||||||||||
12 | and 6
inches from the ceiling.
| ||||||||||||||||||||||||
13 | (b) Every single family residence shall have at least one | ||||||||||||||||||||||||
14 | approved smoke
detector installed on every story of the | ||||||||||||||||||||||||
15 | dwelling unit, including basements
but not including | ||||||||||||||||||||||||
16 | unoccupied attics. In dwelling units with split levels,
a smoke | ||||||||||||||||||||||||
17 | detector installed on the upper level shall suffice for the
| ||||||||||||||||||||||||
18 | adjacent lower level if the lower level is less than one full | ||||||||||||||||||||||||
19 | story below
the upper level; however, if there is an | ||||||||||||||||||||||||
20 | intervening door between the
adjacent levels, a smoke detector | ||||||||||||||||||||||||
21 | shall be installed on each level.
| ||||||||||||||||||||||||
22 | (c) Every structure which (1) contains more than one | ||||||||||||||||||||||||
23 | dwelling unit, or
(2) contains at least one dwelling unit and |
| |||||||
| |||||||
1 | is a mixed-use structure, shall
contain at least one approved | ||||||
2 | smoke detector at the uppermost ceiling of
each interior | ||||||
3 | stairwell. The detector shall be installed on the ceiling,
at | ||||||
4 | least 6 inches from the wall, or on a wall located between 4 | ||||||
5 | and 6
inches from the ceiling.
| ||||||
6 | (d) It shall be the responsibility of the owner of a | ||||||
7 | structure to supply
and install all required detectors. The | ||||||
8 | owner shall be responsible for
making reasonable efforts to | ||||||
9 | test and maintain detectors in common
stairwells and hallways. | ||||||
10 | It shall be the responsibility of a tenant to
test and to | ||||||
11 | provide general maintenance for the detectors within the
| ||||||
12 | tenant's dwelling unit or rooming unit, and to notify the owner | ||||||
13 | or the
authorized agent of the owner in writing of any | ||||||
14 | deficiencies which the
tenant cannot correct. The owner shall | ||||||
15 | be responsible for providing one
tenant per dwelling unit with | ||||||
16 | written information regarding detector
testing and | ||||||
17 | maintenance.
| ||||||
18 | The tenant shall be responsible for replacement of any | ||||||
19 | required batteries
in the smoke detectors in the tenant's | ||||||
20 | dwelling unit, except that the owner
shall ensure that such | ||||||
21 | batteries are in operating condition at the time
the tenant | ||||||
22 | takes possession of the dwelling unit. The tenant shall provide
| ||||||
23 | the owner or the authorized agent of the owner with access to | ||||||
24 | the dwelling
unit to correct any deficiencies in the smoke | ||||||
25 | detector which have been
reported in writing to the owner or | ||||||
26 | the authorized agent of the owner.
|
| |||||||
| |||||||
1 | (e) The requirements of this Section shall apply to any | ||||||
2 | dwelling unit
in existence on July 1, 1988, beginning on that | ||||||
3 | date. Except as provided
in subsections (f) and (g), the smoke | ||||||
4 | detectors required in such dwelling
units may be either battery | ||||||
5 | powered , provided the battery is non-replaceable, | ||||||
6 | non-removable, and capable of powering the detector for a | ||||||
7 | minimum of 10 years, or wired into the structure's AC power
| ||||||
8 | line, and need not be interconnected.
| ||||||
9 | (f) In the case of any dwelling unit that is newly | ||||||
10 | constructed,
reconstructed, or substantially remodelled after | ||||||
11 | December 31, 1987, the
requirements of this Section shall apply | ||||||
12 | beginning on the first day of
occupancy of the dwelling unit | ||||||
13 | after such construction, reconstruction or
substantial | ||||||
14 | remodelling. The smoke detectors required in such dwelling
unit | ||||||
15 | shall be permanently wired into the structure's AC power line, | ||||||
16 | and if
more than one detector is required to be installed | ||||||
17 | within the dwelling
unit, the detectors shall be wired so that | ||||||
18 | the actuation of one detector
will actuate all the detectors in | ||||||
19 | the dwelling unit.
| ||||||
20 | In the case of any dwelling unit that is newly constructed,
| ||||||
21 | reconstructed, or substantially remodeled on or after January | ||||||
22 | 1, 2011, smoke detectors permanently wired into the structure's | ||||||
23 | AC power line must also maintain an alternative back-up power | ||||||
24 | source, which may be either a battery or batteries or an | ||||||
25 | emergency generator. | ||||||
26 | (g) Every hotel shall be equipped with operational portable
|
| |||||||
| |||||||
1 | smoke-detecting alarm devices for the deaf and hearing impaired | ||||||
2 | of audible
and visual design, available for units of occupancy.
| ||||||
3 | Specialized smoke-detectors for the deaf and hearing | ||||||
4 | impaired shall be
available upon request by guests in such | ||||||
5 | hotels at a rate
of at least one such smoke detector per 75 | ||||||
6 | occupancy units or portions
thereof, not to exceed 5 such smoke | ||||||
7 | detectors per hotel.
Incorporation or connection into an | ||||||
8 | existing interior alarm system, so as
to be capable of being | ||||||
9 | activated by the system, may be utilized in lieu of
the | ||||||
10 | portable alarms.
| ||||||
11 | Operators of any hotel shall post conspicuously at the main | ||||||
12 | desk a
permanent notice, in letters at least 3 inches in | ||||||
13 | height, stating that
smoke detector alarm devices for the deaf | ||||||
14 | and hearing impaired are
available. The proprietor may require | ||||||
15 | a refundable deposit for a portable
smoke detector not to | ||||||
16 | exceed the cost of the detector.
| ||||||
17 | (g-5) A hotel, as defined in this Act, shall be responsible | ||||||
18 | for installing and maintaining smoke detecting equipment. | ||||||
19 | (h) Compliance with an applicable federal, State or local | ||||||
20 | law or
building code which requires the installation and | ||||||
21 | maintenance of smoke
detectors in a manner different from this | ||||||
22 | Section, but providing a level of
safety for occupants which is | ||||||
23 | equal to or greater than that provided by
this Section, shall | ||||||
24 | be deemed to be in compliance with this Section, and
the | ||||||
25 | requirements of such more stringent law shall govern over the
| ||||||
26 | requirements of this Section.
|
| |||||||
| |||||||
1 | (i) The requirements of this Section shall not apply to | ||||||
2 | dwelling units and hotels within municipalities with a | ||||||
3 | population over 1,000,000 inhabitants. | ||||||
4 | (Source: P.A. 96-1292, eff. 1-1-11; 97-447, eff. 1-1-12.)
| ||||||
5 | Section 99. Effective date. This Act takes effect January | ||||||
6 | 1, 2014.
|