1 | AN ACT concerning regulation.
| |||||||||||||||||||||||||
2 | Be it enacted by the People of the State of Illinois,
| |||||||||||||||||||||||||
3 | represented in the General Assembly:
| |||||||||||||||||||||||||
4 | Section 5. The Fire Sprinkler Contractor Licensing Act is | |||||||||||||||||||||||||
5 | amended by changing Sections 10, 15, 30, and 65 as follows:
| |||||||||||||||||||||||||
6 | (225 ILCS 317/10)
| |||||||||||||||||||||||||
7 | Sec. 10. Definitions. As used in this Act, unless the | |||||||||||||||||||||||||
8 | context otherwise
requires:
| |||||||||||||||||||||||||
9 | "Designated certified person" means an individual who has | |||||||||||||||||||||||||
10 | met the
qualifications set forth
under Section 20 of this Act.
| |||||||||||||||||||||||||
11 | "Fire protection system layout documents" means layout | |||||||||||||||||||||||||
12 | drawings, catalog information on standard products, and other | |||||||||||||||||||||||||
13 | construction data that provide detail on the location of | |||||||||||||||||||||||||
14 | risers, cross mains, branch lines, sprinklers, piping per | |||||||||||||||||||||||||
15 | applicable standard, and hanger locations. "Fire protection | |||||||||||||||||||||||||
16 | system layout documents" serve as a guide for fabrication and | |||||||||||||||||||||||||
17 | installation of a fire sprinkler system and shall be based upon | |||||||||||||||||||||||||
18 | applicable standards pursuant to Section 30 of this Act.
| |||||||||||||||||||||||||
19 | "Fire pump assembly" means the fire pumps, jockey pumps, | |||||||||||||||||||||||||
20 | and pump controllers but does not include the interconnected | |||||||||||||||||||||||||
21 | pipe, fittings, valves, and other similar parts attached to the | |||||||||||||||||||||||||
22 | automatic fire sprinkler system. | |||||||||||||||||||||||||
23 | "Fire sprinkler contractor" means a person who holds |
| |||||||
| |||||||
1 | himself or herself out
to
be in the
business of or contracts | ||||||
2 | with a person to install or repair a fire sprinkler
system.
| ||||||
3 | "Fire sprinkler system" means any water-based automatic | ||||||
4 | fire extinguishing
system employing
fire sprinklers, including | ||||||
5 | accessory fire pumps and associated piping, fire
standpipes, or
| ||||||
6 | underground fire main systems starting at the
connection to the | ||||||
7 | water service after the approved backflow
device
is installed | ||||||
8 | under the requirements of the Illinois Plumbing Code and ending | ||||||
9 | at
the most
remote fire sprinkler. "Fire sprinkler system" | ||||||
10 | includes but is not
limited to a fire sprinkler
system in a | ||||||
11 | residential, commercial, institutional, educational, public, | ||||||
12 | or
private occupancy.
"Fire sprinkler system" does not include | ||||||
13 | single sprinkler heads that are in
a loop of the potable water | ||||||
14 | system, as referenced in 77 Ill. Adm. Code 890.1130
and | ||||||
15 | 890.1200.
| ||||||
16 | "Licensee" means a person or business organization | ||||||
17 | licensed in accordance
with this Act.
| ||||||
18 | "NICET" means the National Institute for Certification in | ||||||
19 | Engineering
Technologies.
| ||||||
20 | "Person" means an individual, group of individuals, | ||||||
21 | association, trust,
partnership,
corporation, person doing | ||||||
22 | business under an assumed name, the State of
Illinois, or | ||||||
23 | department
thereof, any other state-owned and operated | ||||||
24 | institution, or any other entity.
| ||||||
25 | "Supervision" means the direction and management by a | ||||||
26 | designated certified
person of the
activities of non-certified |
| |||||||
| |||||||
1 | personnel in the installation or repair of fire
sprinkler | ||||||
2 | systems.
| ||||||
3 | (Source: P.A. 94-367, eff. 1-1-06.)
| ||||||
4 | (225 ILCS 317/15)
| ||||||
5 | Sec. 15. Licensing requirements.
| ||||||
6 | (a) It shall be unlawful for any person or business to | ||||||
7 | engage in, advertise,
or hold
itself out to be
in the business | ||||||
8 | of installing or repairing fire sprinkler systems in this State
| ||||||
9 | after 6 months after
the effective date of this Act, unless | ||||||
10 | such person or business is licensed by
the State
Fire Marshal.
| ||||||
11 | (b) In order to obtain a license, a person or business must | ||||||
12 | submit an
application to the State
Fire Marshal, on a form | ||||||
13 | provided by the State Fire Marshal containing the
information | ||||||
14 | prescribed,
along with the application fee.
| ||||||
15 | (c) A business applying for a license must have a | ||||||
16 | designated certified person employed at the
business location | ||||||
17 | and the designated certified person shall be identified on the | ||||||
18 | license application.
| ||||||
19 | (d) A person or business applying for a license must show | ||||||
20 | proof of having liability and
property damage insurance in such | ||||||
21 | amounts and under such circumstances as may
be determined by | ||||||
22 | the
State Fire Marshal.
The amount of liability and property | ||||||
23 | damage insurance, however, shall not be
less than
the amount | ||||||
24 | specified in Section 35 of this Act.
| ||||||
25 | (e) A person or business applying for a license must show |
| |||||||
| |||||||
1 | proof of having
workers' compensation
insurance covering its | ||||||
2 | employees or be approved as a self-insurer of workers'
| ||||||
3 | compensation in
accordance with the laws of this State.
| ||||||
4 | (f) A person or business so licensed shall have a separate | ||||||
5 | license for each
business location
within the State or outside | ||||||
6 | the State when the business location is responsible
for any | ||||||
7 | installation
or repair of fire sprinkler systems performed | ||||||
8 | within the State.
| ||||||
9 | (g) When an individual proposes to do business in her or | ||||||
10 | his own name, a
license, when granted,
shall be issued only to | ||||||
11 | that individual.
| ||||||
12 | (h) If the applicant requesting licensure to engage in | ||||||
13 | contracting is a
business organization,
such as a partnership, | ||||||
14 | corporation, business trust, or other legal entity, the
| ||||||
15 | application shall
state the name of the partnership and its | ||||||
16 | partners, the name of the corporation
and its officers and
| ||||||
17 | directors, the name of the business trust and its trustees, or | ||||||
18 | the name of such
other legal entity
and its members and shall | ||||||
19 | furnish evidence of statutory compliance if a
fictitious name | ||||||
20 | is used. Such
application shall also show that the business | ||||||
21 | entity employs a designated
certified person as
required under | ||||||
22 | Section 20. The license, when issued upon application of a
| ||||||
23 | business organization,
shall be in the name of the business | ||||||
24 | organization and the name of the
qualifying designated | ||||||
25 | certified
person shall be noted thereon.
| ||||||
26 | (i) No license is required for a person or business that is
|
| |||||||
| |||||||
1 | engaged in the installation of fire sprinkler systems only in
| ||||||
2 | single family or multiple family residential dwellings up to | ||||||
3 | and including 8
family units that do not exceed 2 1/2 stories | ||||||
4 | in height from the lowest grade
level.
| ||||||
5 | (j) All fire protection system layout documents of fire | ||||||
6 | sprinkler systems, as defined in Section 10 of this Act, shall | ||||||
7 | be prepared by (i) a professional engineer who is licensed | ||||||
8 | under the Professional Engineering Practice Act of 1989, (ii) | ||||||
9 | an architect who is licensed under the Illinois Architecture | ||||||
10 | Practice Act of 1989, or (iii) a holder of a valid NICET level | ||||||
11 | 3 or 4 certification in fire protection technology automatic | ||||||
12 | sprinkler system layout who is either licensed under this Act | ||||||
13 | or employed by an organization licensed under this Act.
| ||||||
14 | (k) A person or business that seeks a license renewal as a | ||||||
15 | fire sprinkler contractor must provide evidence of at least one | ||||||
16 | fire sprinkler permit legally issued to the person or business | ||||||
17 | named on the application for each of the 2 prior calendar | ||||||
18 | years. Permits must have been issued from a jurisdiction with | ||||||
19 | legal standing and authority to issue permits for fire | ||||||
20 | sprinkler system installation or modification, excluding work | ||||||
21 | solely limited to fire pump assembly. | ||||||
22 | (Source: P.A. 97-112, eff. 7-14-11.)
| ||||||
23 | (225 ILCS 317/30)
| ||||||
24 | Sec. 30. Requirements for the installation, repair, | ||||||
25 | inspection, and testing of fire protection
systems.
|
| |||||||
| |||||||
1 | (a) Equipment shall be listed by a nationally recognized | ||||||
2 | testing laboratory,
such as
Underwriters Laboratories, Inc. or | ||||||
3 | Factory Mutual Laboratories, Inc., or shall
comply with | ||||||
4 | nationally
accepted standards. The State Fire Marshal shall | ||||||
5 | adopt by rule procedures for
determining
whether a laboratory | ||||||
6 | is
nationally recognized, taking into account the laboratory's | ||||||
7 | facilities,
procedures, use of nationally
recognized | ||||||
8 | standards, and any other criteria reasonably calculated to | ||||||
9 | reach an
informed
determination.
| ||||||
10 | (b) Equipment shall be installed in accordance with the | ||||||
11 | applicable standards
of the National
Fire Protection | ||||||
12 | Association and the manufacturer's specifications.
| ||||||
13 | (c) The contractor shall furnish the user with operating | ||||||
14 | instructions for
all equipment
installed, together with a | ||||||
15 | diagram of the final installation.
| ||||||
16 | (d) All fire sprinkler systems shall have a backflow | ||||||
17 | prevention device or,
in a municipality with a population over | ||||||
18 | 500,000, a double detector check
assembly installed by a | ||||||
19 | licensed plumber before the fire sprinkler system
connection to | ||||||
20 | the water service. Connection to the backflow prevention device
| ||||||
21 | or, in a municipality with a population over 500,000, a double | ||||||
22 | detector
assembly shall be done in a manner consistent with the | ||||||
23 | Department of Public
Health's Plumbing Code.
| ||||||
24 | (e) This licensing Act is not intended to require any | ||||||
25 | additional fire
inspections at State level.
| ||||||
26 | (f) Inspections and testing of existing fire sprinkler |
| |||||||
| |||||||
1 | systems and control equipment must be performed by a licensee | ||||||
2 | or an individual employed or contracted by a licensee. Any | ||||||
3 | individual who performs inspection and testing duties under | ||||||
4 | this subsection (f) must possess proof of (i) certification by | ||||||
5 | a nationally recognized certification organization at an | ||||||
6 | appropriate level, such as NICET Level II in Inspection and | ||||||
7 | Testing of Water Based Systems or the equivalent, by January 1, | ||||||
8 | 2009 or (ii) satisfactory completion of a certified sprinkler | ||||||
9 | fitter apprenticeship program approved by the U.S. Department | ||||||
10 | of Labor. State employees who perform inspections and testing | ||||||
11 | on behalf of State institutions and who meet all other | ||||||
12 | requirements of this subsection (f) need not be licensed under | ||||||
13 | this Act or employed by a licensee under this Act in order to | ||||||
14 | perform inspection and testing duties under this subsection | ||||||
15 | (f). The requirements of this subsection (f) do not apply to | ||||||
16 | individuals performing inspections or testing of fire | ||||||
17 | sprinkler systems on behalf of a municipality, a county, a fire | ||||||
18 | protection district, or the Office of the State Fire Marshal. | ||||||
19 | This subsection (f) does not apply to cursory
weekly and | ||||||
20 | monthly inspections of gauges and control valves conducted in
| ||||||
21 | accordance with the standards of the National Fire Protection | ||||||
22 | Association and pump tests that are performed by individuals | ||||||
23 | certified by the pump manufacturer .
| ||||||
24 | A copy of the inspection report for an inspection performed | ||||||
25 | pursuant to this subsection (f) must be forwarded by the entity | ||||||
26 | performing the inspection to the local fire department or fire |
| |||||||
| |||||||
1 | protection district in which the sprinkler system is located. | ||||||
2 | The inspection report must include the NICET Level II | ||||||
3 | Inspection and Testing of Water Based Systems certification | ||||||
4 | number or journeymen number of the person performing the | ||||||
5 | inspection. | ||||||
6 | (Source: P.A. 96-256, eff. 1-1-10; 97-112, eff. 7-14-11.)
| ||||||
7 | (225 ILCS 317/65)
| ||||||
8 | Sec. 65. Notice; suspension, revocation, or refusal to | ||||||
9 | renew a license.
| ||||||
10 | (a) Whenever the State Fire Marshal determines that there | ||||||
11 | are reasonable
grounds to believe
that a licensee has violated | ||||||
12 | a provision of this Act or the rules adopted
under this Act, | ||||||
13 | the
State Fire Marshal shall give notice of the alleged | ||||||
14 | violation to the person
whom the license was
issued. The notice | ||||||
15 | shall (i) be in writing; (ii) include a statement of the
| ||||||
16 | alleged violation which
necessitates issuance of the notice; | ||||||
17 | (iii) contain an outline of remedial
action that, if taken, | ||||||
18 | will
effect compliance with the provisions of this Act and the | ||||||
19 | rules adopted under
this Act; (iv)
prescribe a reasonable time, | ||||||
20 | as determined by the State Fire Marshal, for the
performance of | ||||||
21 | any
action required by the notice; and (v) be served upon the | ||||||
22 | licensee. The
notice shall be deemed to
have been properly | ||||||
23 | served upon the person when a copy of the notice has been
sent | ||||||
24 | by registered or
certified mail to his or her last known | ||||||
25 | address as furnished to the State Fire Marshal or when he or
|
| |||||||
| |||||||
1 | she has been served the notice by any other method authorized | ||||||
2 | by law.
| ||||||
3 | (b) If the person to whom the notice is served does not | ||||||
4 | comply with the terms of the notice
within the time limitations | ||||||
5 | specified in the notice, the State Fire Marshal may proceed | ||||||
6 | with action
to suspend, revoke, or refuse to issue a license as | ||||||
7 | provided in this Section.
| ||||||
8 | (c) Other requirements of this Act notwithstanding, when | ||||||
9 | the State Fire
Marshal
determines that reasonable grounds exist | ||||||
10 | to indicate that a violation of this
Act has been committed
and | ||||||
11 | the violation is the third separate violation by that person in | ||||||
12 | an 18-month
period, the notice
requirement of subsection (a) of | ||||||
13 | this Section is waived and the State Fire
Marshal may proceed
| ||||||
14 | immediately with action to suspend, revoke, or refuse to issue | ||||||
15 | a license.
| ||||||
16 | (d) In any proceeding to suspend, revoke, or refuse to | ||||||
17 | issue a license, the
State Fire Marshal
shall first serve or | ||||||
18 | cause to be served upon the licensee a written notice of
the | ||||||
19 | State Fire
Marshal's intent to take action. The notice shall | ||||||
20 | specify the way in which the
person has failed to
comply with | ||||||
21 | this Act or any other rules or standards of the State Fire | ||||||
22 | Marshal.
| ||||||
23 | (e) In the case of revocation or suspension, the notice | ||||||
24 | shall require the person to remove or
abate the violation or | ||||||
25 | objectionable condition specified in the notice within 5
days. | ||||||
26 | The State Fire
Marshal may specify a longer period of time as |
| |||||||
| |||||||
1 | it deems necessary. If the
person fails to comply
with the | ||||||
2 | terms and conditions of the revocation or suspension notice | ||||||
3 | within the
time specified by the
State Fire Marshal, the State | ||||||
4 | Fire Marshal may revoke or suspend the license.
| ||||||
5 | (f) In the case of refusal to issue a license, if the | ||||||
6 | person fails to comply
with the Act or
rules or standards | ||||||
7 | promulgated under the Act, or after making a determination that | ||||||
8 | the designated party has a history of acting illegally, | ||||||
9 | fraudulently, incompetently, or with gross negligence, the | ||||||
10 | State Fire Marshal may refuse
to issue a license.
| ||||||
11 | (Source: P.A. 92-871, eff. 1-3-03.)
| ||||||
12 | Section 99. Effective date. This Act takes effect upon | ||||||
13 | becoming law.
|