SB3011 Enrolled |
|
LRB094 15598 LCT 50803 b |
|
|
1 |
| AN ACT concerning public safety.
|
2 |
| Be it enacted by the People of the State of Illinois,
|
3 |
| represented in the General Assembly:
|
4 |
| Section 5. The Boiler and Pressure Vessel Safety Act is |
5 |
| amended by changing Sections 2a, 2b, 4, 5, 8, 10, 11, and 15 as |
6 |
| follows:
|
7 |
| (430 ILCS 75/2a) (from Ch. 111 1/2, par. 3202a)
|
8 |
| Sec. 2a. Nuclear facilities. Notwithstanding any other |
9 |
| provision to
the contrary, the Illinois Emergency Management |
10 |
| Agency
Department
of Nuclear Safety shall have sole |
11 |
| jurisdiction over all boilers and pressure
vessels contained |
12 |
| within or upon or in connection with any nuclear facility
|
13 |
| within this State. The Illinois Emergency Management Agency
|
14 |
| Department of Nuclear Safety shall have the same
authority and |
15 |
| shall have and exercise the same powers and duties in relation
|
16 |
| to those boilers and pressure vessels under this Act as the |
17 |
| Board
or the
State Fire Marshal have and exercise in relation |
18 |
| to all boilers
and pressure vessels in this State that are not |
19 |
| included in this
Section.
Notwithstanding any other provision |
20 |
| to the contrary, the Illinois Emergency Management Agency
|
21 |
| Department of
Nuclear Safety shall establish by rule the types |
22 |
| and frequency of
inspections of boilers and pressure vessels |
23 |
| contained within or upon or in
connection with any nuclear |
24 |
| facility. The rules may provide that multiple
boilers and |
25 |
| pressure vessels in a nuclear power system shall be covered by
|
26 |
| a single inspection certificate. The Illinois Emergency |
27 |
| Management Agency
Department of Nuclear Safety may
enter into |
28 |
| such agreements with the Board or the State Fire Marshal as are
|
29 |
| necessary to carry out its duties under this Act. The |
30 |
| agreements may
provide that the Illinois Emergency Management |
31 |
| Agency
Department of Nuclear Safety shall accept and recognize
|
32 |
| Special Inspector Commissions issued by the State Fire Marshal.
|
|
|
|
SB3011 Enrolled |
- 2 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| (Source: P.A. 86-901; 87-1169.)
|
2 |
| (430 ILCS 75/2b) (from Ch. 111 1/2, par. 3202b)
|
3 |
| Sec. 2b. In addition to its other powers, the Illinois |
4 |
| Emergency Management Agency
Department of Nuclear
Safety is |
5 |
| authorized to enter into agreements with the United States
|
6 |
| Nuclear Regulatory Commission for the establishment of a |
7 |
| coordinated and
comprehensive program to minimize the risks |
8 |
| posed by boilers, pressure
vessels, and related components |
9 |
| contained within or upon or in connection
with any nuclear |
10 |
| facility within this State. The program may provide for
such |
11 |
| inspections of nuclear facilities within the State as may be |
12 |
| agreed
upon and for inspections within and outside the State of |
13 |
| Illinois of
boilers and pressure vessels to be installed in any |
14 |
| nuclear facility within
this State.
|
15 |
| (Source: P.A. 86-901.)
|
16 |
| (430 ILCS 75/4) (from Ch. 111 1/2, par. 3205)
|
17 |
| Sec. 4. Existing
boilers and pressure vessels.
|
18 |
| (a) The maximum allowable pressure consistent with the |
19 |
| maximum and
minimum operating temperatures of a boiler carrying |
20 |
| the ASME
Code symbol or of a pressure vessel carrying the ASME |
21 |
| or API-ASME Code
symbol shall be determined by the applicable |
22 |
| section of the Code under
which it was constructed and stamped |
23 |
| or a later edition
of the ASME Code, provided the
rating |
24 |
| conforms with the
rules of the later edition.
|
25 |
| (b) The maximum allowable pressure consistent with the |
26 |
| maximum and
minimum operating temperatures of a boiler or |
27 |
| pressure vessel
that does not carry the ASME or the API-ASME |
28 |
| Code symbol shall be
computed in accordance with the rules and |
29 |
| regulations of the
Board, unless the boiler
or pressure vessel |
30 |
| is of special design or
construction, in which case the Board |
31 |
| may grant, at its discretion, a special
operating permit |
32 |
| consistent with the safety objectives of the rules and
|
33 |
| regulations of the Board.
|
34 |
| (c) This Act does not prohibit the use,
sale, or |
|
|
|
SB3011 Enrolled |
- 3 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| reinstallation of
a boiler or pressure vessel
referred to in |
2 |
| this Section, provided it has
been made to conform to the rules |
3 |
| and regulations of the Board
governing existing installations, |
4 |
| and provided, further, it has not been
found upon inspection to |
5 |
| be in an unsafe condition.
|
6 |
| (Source: P.A. 87-1169.)
|
7 |
| (430 ILCS 75/5) (from Ch. 111 1/2, par. 3206)
|
8 |
| Sec. 5. Exemptions.
|
9 |
| (a) This Act shall not apply to the following boilers and |
10 |
| pressure vessels:
|
11 |
| (1) Boilers and pressure vessels under federal |
12 |
| regulations, except for
boiler and pressure vessels in |
13 |
| nuclear facilities subject to Section 2a, and
boilers and |
14 |
| pressure vessels located in cities of more than 500,000
|
15 |
| inhabitants.
|
16 |
| (2) Pressure vessels used for transportation and |
17 |
| storage of
compressed or liquefied gases when constructed |
18 |
| in compliance with
specifications of the Department of |
19 |
| Transportation and charged with
gas or liquid, marked, |
20 |
| maintained, and periodically requalified for use,
as |
21 |
| required by appropriate regulations of the Department of
|
22 |
| Transportation.
|
23 |
| (3) Pressure vessels located on vehicles operating |
24 |
| under the rules of
other State authorities and used for |
25 |
| carrying passengers or freight.
|
26 |
| (4) Pressure vessels installed on the right of way of |
27 |
| railroads and
used directly in the operation of trains.
|
28 |
| (5) Boilers and pressure vessels under the inspection |
29 |
| jurisdiction of the
Department of Natural Resources and |
30 |
| located on mine
property.
|
31 |
| (6) Boilers and pressure vessels located on farms and |
32 |
| used solely for
agricultural purposes.
|
33 |
| (7) Steam boilers of a miniature model locomotive, |
34 |
| boat, tractor,
or stationary engine constructed and |
35 |
| maintained as a hobby and not for
commercial use, that have |
|
|
|
SB3011 Enrolled |
- 4 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| an inside diameter not exceeding 12 inches and a
grate area |
2 |
| not exceeding 1 1/2 square feet, provided they are |
3 |
| constantly
attended while in operation and are equipped |
4 |
| with a water level indicator,
pressure gauge, and a safety |
5 |
| valve of adequate capacity.
|
6 |
| (8) Pressure vessels regulated and inspected under the |
7 |
| Illinois
Fertilizer Act of 1961.
|
8 |
| (9) Pressure vessels containing liquified petroleum |
9 |
| gas regulated under
the Liquified Petroleum Gas Regulation |
10 |
| Act , except those used for industrial
processes .
|
11 |
| (b) The following boilers and pressure vessels shall be |
12 |
| exempt from
the requirements of Sections 10, 11, 12, and 13 of |
13 |
| this Act:
|
14 |
| (1) Steam boilers used for heating purposes and |
15 |
| operated at a
pressure not in excess of 15 pounds per |
16 |
| square inch gauge (psig)
and having a rating not in excess |
17 |
| of 200,000 B.T.U. per hour input.
|
18 |
| (2) Hot water heating boilers operated at a pressure |
19 |
| not in excess of
30 psig and having a rating not in excess |
20 |
| of 200,000 B.T.U. per hour.
|
21 |
| (3) Boilers and pressure vessels, located in private |
22 |
| residences or in
multi-family buildings having fewer than 6 |
23 |
| dwelling units .
|
24 |
| (4) Hot water supply boilers that are directly fired |
25 |
| with oil, gas, or electricity when none of the following |
26 |
| limitations are exceeded:
|
27 |
| (A) Heat input of 200,000 BTU per hour.
|
28 |
| (B) Water temperature of 200 degrees Fahrenheit.
|
29 |
| (C) Nominal water containing capacity of 120 U.S. |
30 |
| gallons.
|
31 |
| (5) Coil type hot water boilers where the water can |
32 |
| flash into steam when released directly to the atmosphere |
33 |
| through a manually operated nozzle provided the following |
34 |
| conditions are met:
|
35 |
| (A) There is no drum, headers, or other steam |
36 |
| space.
|
|
|
|
SB3011 Enrolled |
- 5 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| (B) No steam is generated within the coil.
|
2 |
| (C) Outside diameter of tubing does not exceed 1 |
3 |
| inch.
|
4 |
| (D) Pipe size does not exceed 3/4 inch NPS.
|
5 |
| (E) Water capacity of unit does not exceed 6 U.S. |
6 |
| gallons.
|
7 |
| (F) Water temperature does not exceed 350 degrees |
8 |
| Fahrenheit.
|
9 |
| , that are within
any of the following categories:
|
10 |
| (A) Steam heating boilers operated at not more than |
11 |
| 15 psig.
|
12 |
| (B) Hot water heating boilers operated at not more |
13 |
| than 30 psig.
|
14 |
| (C) Hot water boilers operated at not more than 160 |
15 |
| psig
or 250 degrees Fahrenheit.
|
16 |
| (6)
(D) Pressure vessels containing only water under |
17 |
| pressure for
domestic supply purposes, including those |
18 |
| containing air, the compression
of which serves only a |
19 |
| cushion or airlift pumping function.
|
20 |
| (7)Pressure vessels operated at a pressure not |
21 |
| exceeding 15 psig with no limitation on size.
|
22 |
| (8) Pressure vessels that do not exceed:
|
23 |
| (A) Both a volume of 15 cubic feet and 250 psig |
24 |
| when not located in a place of public assembly.
|
25 |
| (B) Both a volume of 5 cubic and 250 psig when |
26 |
| located in a place of public assembly.
|
27 |
| (C) A volume of 1 1/2 cubic feet or an inside |
28 |
| diameter of 6 inches with no limitation on pressure.
|
29 |
| (9) Water conditioning equipment used for the removal |
30 |
| of minerals, chemicals, or organic or inorganic particles |
31 |
| from water by means other than application of heat |
32 |
| including, without limitation, water softeners, water |
33 |
| filters, dealkalizers, and demineralizers.
|
34 |
| (10) Steam boilers of railroad locomotives and |
35 |
| traction engines built prior
to 1955 that were constructed |
36 |
| or operated
in compliance with the Federal Locomotive |
|
|
|
SB3011 Enrolled |
- 6 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| Inspection Law and are in the
permanent collection of a |
2 |
| museum or historical association are exempt
from the |
3 |
| requirements of subsection (c) of Section 10 upon proof of
|
4 |
| such construction or inspection being furnished to the |
5 |
| Board.
|
6 |
| (c) (Blank).
Steam boilers of railroad locomotives and |
7 |
| traction engines built prior
to 1955 that were constructed or |
8 |
| operated
in compliance with the Federal Locomotive Inspection |
9 |
| Law and are in the
permanent collection of a museum or |
10 |
| historical association are exempt
from the requirements of |
11 |
| subsection (c) of Section 10 upon proof of
such construction or |
12 |
| inspection being furnished to the Board.
|
13 |
| (Source: P.A. 88-608, eff. 1-1-95; 88-616, eff. 9-9-94;
89-235, |
14 |
| eff. 8-4-95; 89-445, eff. 2-7-96.)
|
15 |
| (430 ILCS 75/8) (from Ch. 111 1/2, par. 3209)
|
16 |
| Sec. 8. Special Inspectors.
|
17 |
| (a) The
Office of the State Fire Marshal shall, upon the |
18 |
| request of
any company authorized to write boiler and pressure |
19 |
| vessel insurance
in this State or authorized under Section 15 |
20 |
| of this Act to self-insure
boilers and pressure vessels , issue |
21 |
| to inspectors of the company
commissions as Special Inspectors, |
22 |
| provided that each inspector
before receiving his commission |
23 |
| shall meet the experience requirements of
the Board and shall:
|
24 |
| (1) satisfactorily pass the
examination provided for |
25 |
| in Section 9 of this Act; or
|
26 |
| (2) in lieu of that
examination, hold a Certificate of |
27 |
| Competency as an inspector of
boilers or pressure vessels |
28 |
| for a jurisdiction that has a standard of
examination |
29 |
| substantially equal to that of the State of Illinois; or
|
30 |
| (3) hold a
Commission as an inspector of boilers and |
31 |
| pressure
vessels from the National Board of Boiler
and |
32 |
| Pressure Vessel Inspectors.
|
33 |
| (b) Special Inspectors shall receive no salary from, nor |
34 |
| shall
any of their expenses be paid by, the State. The |
35 |
| continuance of a
Special Inspector's Commission shall be |
|
|
|
SB3011 Enrolled |
- 7 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| conditioned upon his continuing
in the employ of the duly |
2 |
| authorized insurance company or
owner-user
self-insurer and |
3 |
| upon maintenance of the standards
imposed by this Act.
|
4 |
| (c) Special Inspectors shall inspect boilers and pressure
|
5 |
| vessels insured or operated
self-insured by their respective |
6 |
| companies.
The Board may impose limitations on owner-user |
7 |
| inspectors who have
received their commissions based on the |
8 |
| American Petroleum Institute API-510
Inspectors Examination. |
9 |
| When
so inspected, the owners and users of insured or |
10 |
| self-insured
boilers and pressure
vessels shall be exempt from |
11 |
| the payment to the State of the inspection
fees provided for in |
12 |
| Section 13 of this Act.
|
13 |
| (d) Within 10 business days
30
days following each boiler |
14 |
| or pressure vessel certificate inspection,
except the |
15 |
| inspection of pressure vessels covered by subsection (c)
of |
16 |
| Section 11 of this Act, made by
a Special Inspector, the |
17 |
| company employing the
inspector shall file a report of the |
18 |
| inspection with the Chief
Inspector either electronically or |
19 |
| upon the appropriate forms. Reports of non-certificate |
20 |
| external inspections need
not be submitted except when those
|
21 |
| inspections disclose that the boiler or
pressure vessel is in |
22 |
| an unsafe condition or in
violation of the rules and |
23 |
| regulations of the Board.
|
24 |
| (e) The State Fire Marshal, the Chief
Inspector, or any |
25 |
| Deputy or Special Inspector, shall have free access to any
|
26 |
| premises in the State to perform
inspections and investigations |
27 |
| in accordance with the
provisions of this Act.
|
28 |
| (Source: P.A. 87-1169; 88-608, eff. 1-1-95.)
|
29 |
| (430 ILCS 75/10) (from Ch. 111 1/2, par. 3211)
|
30 |
| Sec. 10. Inspection of boilers and pressure vessels.
|
31 |
| (a) Each boiler
or pressure vessel used or proposed to be |
32 |
| used within this State, except
boilers or pressure vessels |
33 |
| exempt under this Act or rules and regulations of
the Board, |
34 |
| shall be
thoroughly inspected as to its construction, |
35 |
| installation, condition, and
operation as follows:
|
|
|
|
SB3011 Enrolled |
- 8 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| (1) Power boilers shall be inspected annually both |
2 |
| internally
and
externally while not under pressure and |
3 |
| shall also be inspected annually
externally while under |
4 |
| pressure if possible; provided that any power
boiler or |
5 |
| steam generator, the operation of which is an integral part |
6 |
| of
or a necessary adjunct to other continuous processing |
7 |
| operations, shall
be inspected internally at such |
8 |
| intervals as are permitted by the
shutting down of the |
9 |
| processing operations. The Board may provide by
rules and |
10 |
| regulations for extension of time within which power |
11 |
| boilers
are required to be inspected based upon type, |
12 |
| function, or manner of
operation.
|
13 |
| (2) Low pressure steam ,
and hot water heating ,
boilers |
14 |
| and hot water
supply boilers shall be inspected
biennially |
15 |
| as required by the rules and regulations of the Board.
|
16 |
| (3) Traction steam engine boilers and other boilers |
17 |
| constructed
before the effective date of this amendatory |
18 |
| Act of 1992 and operated solely
for exhibition purposes may |
19 |
| be issued an inspection certificate by the
Chief or Deputy |
20 |
| Inspector, provided the owner can establish and document
|
21 |
| that the design, materials, fabrication, examination, |
22 |
| testing, and operation
are in accordance with the rules and |
23 |
| regulations of the Board. Traction
engine boilers and other |
24 |
| boilers used solely for exhibition purposes
shall be |
25 |
| inspected every 2 years.
|
26 |
| (4) Pressure vessels subject to internal corrosion |
27 |
| shall receive a
certificate inspection every 3 years as |
28 |
| required by rules and regulations of
the
Board. However, |
29 |
| the standards of inspection and repair of pressure
vessels |
30 |
| in service by an owner-user authorized under
Section 15 |
31 |
| shall, at
the option of the owner -user
or user , be either |
32 |
| (1) the applicable rules and
regulations in the National |
33 |
| Board Inspection Code, or (2) the applicable section
|
34 |
| standards in the
American Petroleum Institute API-510, |
35 |
| "API Recommended Practice for Inspection, Repair, and |
36 |
| Rating
of Pressure Vessels in Petroleum Refining Service" , |
|
|
|
SB3011 Enrolled |
- 9 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| with any revisions,
reissues, amendments, and |
2 |
| interpretations of those
inspection standards that are |
3 |
| subsequently approved and adopted by the Board .
|
4 |
| (5) Pressure vessels not subject to internal corrosion |
5 |
| shall receive
certificate inspection at intervals set by |
6 |
| the Board, but internal
inspection shall not be required of |
7 |
| pressure vessels containing materials that
are known to be |
8 |
| noncorrosive to the material of which the shell,
heads, or |
9 |
| fittings are constructed, either from the chemical |
10 |
| composition
of the materials or from evidence that the |
11 |
| materials are adequately
treated with a corrosion |
12 |
| inhibitor, provided that the vessels are
constructed in |
13 |
| accordance with the rules and regulations of the Board.
|
14 |
| A grace period of 2 months beyond the period specified in |
15 |
| this Section
may elapse between internal
inspections of a |
16 |
| boiler while it is not under pressure and between external
|
17 |
| inspections of a boiler while it is under pressure. The Board |
18 |
| may, in its
discretion, permit longer periods between |
19 |
| certificate inspection.
|
20 |
| The inspections herein required shall be made by the Chief |
21 |
| Inspector, a
Deputy Inspector, or a Special Inspector provided |
22 |
| for in this
Act.
|
23 |
| (b) If at any time a test is deemed necessary for a stated |
24 |
| cause by
the inspector, the owner or user shall perform a
test |
25 |
| acceptable to the inspector in the
presence of and under the |
26 |
| direction of the
inspector.
|
27 |
| (c) All boilers and pressure vessels, except those
|
28 |
| otherwise exempted by the Board, shall be inspected during
|
29 |
| construction, as required by the applicable rules and |
30 |
| regulations of the
Board, by an inspector authorized to inspect |
31 |
| boilers and pressure vessels
in this State or, if constructed |
32 |
| outside of the State, by an inspector
holding a Certificate |
33 |
| from the National Board of Boiler and Pressure
Vessel |
34 |
| Inspectors or a Certificate of Competency as an inspector of
|
35 |
| boilers and pressure vessels for a jurisdiction that has a |
36 |
| standard of
examination substantially equal to that of this |
|
|
|
SB3011 Enrolled |
- 10 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| State as provided in
Section 9.
|
2 |
| (Source: P.A. 87-1169; 88-608, eff. 1-1-95.)
|
3 |
| (430 ILCS 75/11) (from Ch. 111 1/2, par. 3212)
|
4 |
| Sec. 11. Inspection Certificates and annual statements.
|
5 |
| (a) Each
company employing Special Inspectors, except a |
6 |
| company operating
pressure vessels covered by an owner-user |
7 |
| inspection
service , that meet the
requirements of subsection |
8 |
| (a) of Section 8 of this Act shall, within
10 business days
30 |
9 |
| days following each certificate inspection, file a report of |
10 |
| inspection with
the Chief Inspector
electronically or upon the |
11 |
| appropriate forms as approved by the division.
upon appropriate |
12 |
| forms provided by the Division.
|
13 |
| (b) If the report filed pursuant to subsection (a) of this |
14 |
| Section
shows that a boiler or pressure vessel is found to |
15 |
| comply with the
rules and regulations of the Board, the owner |
16 |
| or user thereof shall pay
directly to the Office of the State |
17 |
| Fire Marshal the fee established by the
Board,
and the Chief
|
18 |
| Inspector shall issue to the owner or user
an Inspection |
19 |
| Certificate bearing the date of inspection and specifying
the |
20 |
| maximum pressure under which the boiler or pressure vessel may |
21 |
| be
operated.
Notwithstanding any other provision of this |
22 |
| Section, an Inspection Certificate
shall remain valid beyond |
23 |
| the expiration date noted on the certificate until
the boiler |
24 |
| or pressure vessel is reinspected by the authorized inspecting
|
25 |
| authorities or until the certificate is suspended by the Chief |
26 |
| Inspector,
provided that the owner or user of the boiler or |
27 |
| pressure vessel makes it
available for inspection at reasonable |
28 |
| times. Certificates shall be posted in
the room containing the
|
29 |
| boiler or pressure vessel inspected. If the boiler or pressure |
30 |
| vessel is
not located within the building, the certificate |
31 |
| shall be posted in a
location convenient to the boiler or |
32 |
| pressure vessel inspected or in any
place where it will be |
33 |
| accessible to interested parties.
|
34 |
| (c) Each company operating pressure vessels covered by an |
35 |
| owner-user
inspection program
service meeting the requirements |
|
|
|
SB3011 Enrolled |
- 11 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| of subsection (a) of
Section 8 of this Act shall maintain in |
2 |
| its files an inspection record,
which shall list, by number and |
3 |
| such abbreviated description as may be
necessary for |
4 |
| identification, each pressure vessel covered by this Act,
the |
5 |
| date of the last inspection of each unit, and the approximate |
6 |
| date for the
next inspection. The inspection date
shall be |
7 |
| arrived at by applying the appropriate rules to all data
|
8 |
| available at the time the inspection record is compiled. The
|
9 |
| inspection record shall be readily available for examination by |
10 |
| the
Chief Inspector or his authorized representative during |
11 |
| business hours.
Each such company shall, in addition, file |
12 |
| annually with the Chief
Inspector a statement, signed by the |
13 |
| person having supervision over
the inspections made during the |
14 |
| period covered, stating the number of
vessels covered by this |
15 |
| Act inspected during the year and certifying
that each |
16 |
| inspection was conducted pursuant to the inspection
standards |
17 |
| provided for by this Act. The annual statement shall be
|
18 |
| accompanied by the
a filing fee in accordance with the rates |
19 |
| established by the
Board.
|
20 |
| (d) (Blank).
An Inspection Certificate issued for a boiler |
21 |
| or
pressure vessel based upon a report of a Special Inspector |
22 |
| shall be
void if the boiler or pressure vessel insurance
|
23 |
| ceases.
|
24 |
| (e) The Chief Inspector or his authorized representative |
25 |
| may at any
time suspend an Inspection Certificate when, in his |
26 |
| opinion, the boiler
or pressure vessel for which it was issued |
27 |
| cannot be operated without
menace to public safety, when the |
28 |
| boiler or pressure vessel is
found not to comply with the rules |
29 |
| and regulations herein provided, or
when an owner or operator |
30 |
| has failed to pay any required fees or refused to
allow |
31 |
| inspection. In
that event, the Chief Inspector or his |
32 |
| representative shall issue a Notice
of Suspension, which shall |
33 |
| be posted in a conspicuous location on or near
the posted |
34 |
| Inspection Certificate. Each suspension of an Inspection
|
35 |
| Certificate shall continue in effect until the boiler or |
36 |
| pressure vessel
has been made to conform to the rules and |
|
|
|
SB3011 Enrolled |
- 12 - |
LRB094 15598 LCT 50803 b |
|
|
1 |
| regulations of the Board,
and until the Inspection Certificate |
2 |
| has been reinstated.
|
3 |
| (Source: P.A. 88-608, eff. 1-1-95; 89-467, eff. 1-1-97.)
|
4 |
| (430 ILCS 75/15) (from Ch. 111 1/2, par. 3216)
|
5 |
| Sec. 15. Self-insurers. Any owner or user of boilers or |
6 |
| pressure vessels subject to Section 10 of
this Act who
|
7 |
| maintains and operates, under the supervision of one or more |
8 |
| regularly
employed engineers who meet the experience and
|
9 |
| education requirements of the Board, an inspection or |
10 |
| maintenance program
service in
which one or more inspectors are |
11 |
| regularly employed on inspection of boilers or
pressure vessels |
12 |
| operated by the
owner or
user shall, upon
application to the |
13 |
| Board showing that fact
and showing that the owner or user
has |
14 |
| the financial ability to bear any loss and to pay
all final
|
15 |
| judgments or awards obtained against the owner or user by
|
16 |
| reason of the operation
of the boilers or pressure vessels, be |
17 |
| authorized to act as a self-insurer
of his or its
boiler and |
18 |
| pressure vessel risk in this State; and when
so authorized, the |
19 |
| owner-user shall employ special
inspectors to supervise
|
20 |
| inspections performed at the owner-user's facilities.
The |
21 |
| owner-user and the regularly employed special inspectors shall |
22 |
| be
entitled
to all the
rights and privileges and shall be |
23 |
| subject to all the requirements, duties,
and obligations |
24 |
| provided in this Act respectively for boiler and pressure
|
25 |
| vessel insurance companies and special inspectors.
|
26 |
| (Source: P.A. 87-1169; 88-608, eff. 1-1-95.)
|
27 |
| (430 ILCS 75/14 rep.)
|
28 |
| Section 10. The Boiler and Pressure Vessel Safety Act is |
29 |
| amended by repealing Section 14.
|
30 |
| Section 99. Effective date. This Act takes effect upon |
31 |
| becoming law.
|