| AN ACT concerning safety.
|
2 |
| Be it enacted by the People of the State of Illinois,
|
3 |
| represented in the General Assembly:
|
4 |
| Section 5. The Public Building Egress Act is amended by |
5 |
| adding Section 1.5 as follows: |
6 |
| (425 ILCS 55/1.5 new)
|
7 |
| Sec. 1.5. Stairwell door access. |
8 |
| (a) Stairwell enclosures in buildings greater than 4 |
9 |
| stories shall comply with one of the following requirements: |
10 |
| (1) No stairwell enclosure door shall be locked at any |
11 |
| time in order to provide re-entry from the stair enclosure |
12 |
| to the interior of the building; or |
13 |
| (2) Stairwell enclosure doors that are locked shall be |
14 |
| equipped with an electronic lock release system that is |
15 |
| activated upon loss of power, manually by a single switch |
16 |
| accessible to building management or firefighting |
17 |
| personnel, and automatically by activation of the |
18 |
| building's fire alarm system. |
19 |
| A telephone or other two-way communications system |
20 |
| connected to an approved constantly attended location shall be |
21 |
| provided on not less than every fifth floor in each stairway |
22 |
| where the doors to the stairway are locked. If this option is |
23 |
| selected, the building must comply with these requirements by |
24 |
| January 1, 2006. |
25 |
| (b) Regardless of which option is selected under subsection |
26 |
| (a) of this Section, stairwell enclosure doors at the main |
27 |
| egress level of the building shall remain unlocked from the |
28 |
| stairwell enclosure side at all times. |
29 |
| (c) Building owners that select the option under paragraph |
30 |
| (2) of subsection (a) of this Section must comply with the |
31 |
| following requirements during the time necessary to install a |
32 |
| lock release system and the two-way communication system: |