HB4894 Engrossed |
|
LRB094 18210 RAS 53521 b |
|
|
1 |
| AN ACT concerning regulation.
|
2 |
| Be it enacted by the People of the State of Illinois, |
3 |
| represented in the General Assembly:
|
4 |
| Section 5. The Fire Sprinkler Contractor Licensing Act is |
5 |
| amended by changing Section 30 as follows:
|
6 |
| (225 ILCS 317/30)
|
7 |
| Sec. 30. Requirements for the installation ,
and repair , |
8 |
| inspection, and testing of fire protection
systems.
|
9 |
| (a) Equipment shall be listed by a nationally recognized |
10 |
| testing laboratory,
such as
Underwriters Laboratories, Inc. or |
11 |
| Factory Mutual Laboratories, Inc., or shall
comply with |
12 |
| nationally
accepted standards. The State Fire Marshal shall |
13 |
| adopt by rule procedures for
determining
whether a laboratory |
14 |
| is
nationally recognized, taking into account the laboratory's |
15 |
| facilities,
procedures, use of nationally
recognized |
16 |
| standards, and any other criteria reasonably calculated to |
17 |
| reach an
informed
determination.
|
18 |
| (b) Equipment shall be installed in accordance with the |
19 |
| applicable standards
of the National
Fire Protection |
20 |
| Association and the manufacturer's specifications.
|
21 |
| (c) The contractor shall furnish the user with operating |
22 |
| instructions for
all equipment
installed, together with a |
23 |
| diagram of the final installation.
|
24 |
| (d) All fire sprinkler systems shall have a backflow |
25 |
| prevention device or,
in a municipality with a population over |
26 |
| 500,000, a double detector check
assembly installed by a |
27 |
| licensed plumber before the fire sprinkler system
connection to |
28 |
| the water service. Connection to the backflow prevention device
|
29 |
| or, in a municipality with a population over 500,000, a double |
30 |
| detector
assembly shall be done in a manner consistent with the |
31 |
| Department of Public
Health's Plumbing Code.
|
32 |
| (e) This licensing Act is not intended to require any |