2021 and 2022 HB0051 Introduced 1/14/2021, by Rep. Jaime M. Andrade, Jr. SYNOPSIS AS INTRODUCED: |
| 425 ILCS 60/3 | from Ch. 127 1/2, par. 803 |
|
Amends the Smoke Detector Act. Removes language providing that specified smoke detector requirements shall not apply to dwelling units and hotels within municipalities with a population over 1,000,000 inhabitants.
|
| |
| | A BILL FOR |
|
|
| | HB0051 | | LRB102 03963 CPF 13979 b |
|
|
1 | | AN ACT concerning safety.
|
2 | | Be it enacted by the People of the State of Illinois,
|
3 | | represented in the General Assembly:
|
4 | | Section 5. The Smoke Detector Act is amended by changing |
5 | | Section 3 as follows:
|
6 | | (425 ILCS 60/3) (from Ch. 127 1/2, par. 803)
|
7 | | (Text of Section before amendment by P.A. 100-200 )
|
8 | | Sec. 3.
(a) Every dwelling unit or hotel shall be equipped |
9 | | with at least one
approved smoke detector in an operating |
10 | | condition within 15 feet of every room
used for sleeping |
11 | | purposes. The detector shall be installed on the ceiling
and |
12 | | at least 6 inches from any wall, or on a wall located between 4 |
13 | | and 6
inches from the ceiling.
|
14 | | (b) Every single family residence shall have at least one |
15 | | approved smoke
detector installed on every story of the |
16 | | dwelling unit, including basements
but not including |
17 | | unoccupied attics. In dwelling units with split levels,
a |
18 | | smoke detector installed on the upper level shall suffice for |
19 | | the
adjacent lower level if the lower level is less than one |
20 | | full story below
the upper level; however, if there is an |
21 | | intervening door between the
adjacent levels, a smoke detector |
22 | | shall be installed on each level.
|
23 | | (c) Every structure which (1) contains more than one |
|
| | HB0051 | - 2 - | LRB102 03963 CPF 13979 b |
|
|
1 | | dwelling unit, or
(2) contains at least one dwelling unit and |
2 | | is a mixed-use structure, shall
contain at least one approved |
3 | | smoke detector at the uppermost ceiling of
each interior |
4 | | stairwell. The detector shall be installed on the ceiling,
at |
5 | | least 6 inches from the wall, or on a wall located between 4 |
6 | | and 6
inches from the ceiling.
|
7 | | (d) It shall be the responsibility of the owner of a |
8 | | structure to supply
and install all required detectors. The |
9 | | owner shall be responsible for
making reasonable efforts to |
10 | | test and maintain detectors in common
stairwells and hallways. |
11 | | It shall be the responsibility of a tenant to
test and to |
12 | | provide general maintenance for the detectors within the
|
13 | | tenant's dwelling unit or rooming unit, and to notify the |
14 | | owner or the
authorized agent of the owner in writing of any |
15 | | deficiencies which the
tenant cannot correct. The owner shall |
16 | | be responsible for providing one
tenant per dwelling unit with |
17 | | written information regarding detector
testing and |
18 | | maintenance.
|
19 | | The tenant shall be responsible for replacement of any |
20 | | required batteries
in the smoke detectors in the tenant's |
21 | | dwelling unit, except that the owner
shall ensure that such |
22 | | batteries are in operating condition at the time
the tenant |
23 | | takes possession of the dwelling unit. The tenant shall |
24 | | provide
the owner or the authorized agent of the owner with |
25 | | access to the dwelling
unit to correct any deficiencies in the |
26 | | smoke detector which have been
reported in writing to the |
|
| | HB0051 | - 3 - | LRB102 03963 CPF 13979 b |
|
|
1 | | owner or the authorized agent of the owner.
|
2 | | (e) The requirements of this Section shall apply to any |
3 | | dwelling unit
in existence on July 1, 1988, beginning on that |
4 | | date. Except as provided
in subsections (f) and (g), the smoke |
5 | | detectors required in such dwelling
units may be either |
6 | | battery powered or wired into the structure's AC power
line, |
7 | | and need not be interconnected.
|
8 | | (f) In the case of any dwelling unit that is newly |
9 | | constructed,
reconstructed, or substantially remodelled after |
10 | | December 31, 1987, the
requirements of this Section shall |
11 | | apply beginning on the first day of
occupancy of the dwelling |
12 | | unit after such construction, reconstruction or
substantial |
13 | | remodelling. The smoke detectors required in such dwelling
|
14 | | unit shall be permanently wired into the structure's AC power |
15 | | line, and if
more than one detector is required to be installed |
16 | | within the dwelling
unit, the detectors shall be wired so that |
17 | | the actuation of one detector
will actuate all the detectors |
18 | | in the dwelling unit.
|
19 | | In the case of any dwelling unit that is newly |
20 | | constructed,
reconstructed, or substantially remodeled on or |
21 | | after January 1, 2011, smoke detectors permanently wired into |
22 | | the structure's AC power line must also maintain an |
23 | | alternative back-up power source, which may be either a |
24 | | battery or batteries or an emergency generator. |
25 | | (g) Every hotel shall be equipped with operational |
26 | | portable
smoke-detecting alarm devices for the deaf and |
|
| | HB0051 | - 4 - | LRB102 03963 CPF 13979 b |
|
|
1 | | hearing impaired of audible
and visual design, available for |
2 | | units of occupancy.
|
3 | | Specialized smoke detectors smoke-detectors for the deaf |
4 | | and hearing impaired shall be
available upon request by guests |
5 | | in such hotels at a rate
of at least one such smoke detector |
6 | | per 75 occupancy units or portions
thereof, not to exceed 5 |
7 | | such smoke detectors per hotel.
Incorporation or connection |
8 | | into an existing interior alarm system, so as
to be capable of |
9 | | being activated by the system, may be utilized in lieu of
the |
10 | | portable alarms.
|
11 | | Operators of any hotel shall post conspicuously at the |
12 | | main desk a
permanent notice, in letters at least 3 inches in |
13 | | height, stating that
smoke detector alarm devices for the deaf |
14 | | and hearing impaired are
available. The proprietor may require |
15 | | a refundable deposit for a portable
smoke detector not to |
16 | | exceed the cost of the detector.
|
17 | | (g-5) A hotel, as defined in this Act, shall be |
18 | | responsible for installing and maintaining smoke detecting |
19 | | equipment. |
20 | | (h) Compliance with an applicable federal, State , or local |
21 | | law or
building code which requires the installation and |
22 | | maintenance of smoke
detectors in a manner different from this |
23 | | Section, but providing a level of
safety for occupants which |
24 | | is equal to or greater than that provided by
this Section, |
25 | | shall be deemed to be in compliance with this Section, and
the |
26 | | requirements of such more stringent law shall govern over the
|
|
| | HB0051 | - 5 - | LRB102 03963 CPF 13979 b |
|
|
1 | | requirements of this Section.
|
2 | | (Source: P.A. 96-1292, eff. 1-1-11; 97-447, eff. 1-1-12; |
3 | | revised 8-19-20.)
|
4 | | (Text of Section after amendment by P.A. 100-200 )
|
5 | | Sec. 3.
(a) Every dwelling unit or hotel shall be equipped |
6 | | with at least one
approved smoke detector in an operating |
7 | | condition within 15 feet of every room
used for sleeping |
8 | | purposes. The detector shall be installed on the ceiling
and |
9 | | at least 6 inches from any wall, or on a wall located between 4 |
10 | | and 6
inches from the ceiling.
|
11 | | (b) Every single family residence shall have at least one |
12 | | approved smoke
detector installed on every story of the |
13 | | dwelling unit, including basements
but not including |
14 | | unoccupied attics. In dwelling units with split levels,
a |
15 | | smoke detector installed on the upper level shall suffice for |
16 | | the
adjacent lower level if the lower level is less than one |
17 | | full story below
the upper level; however, if there is an |
18 | | intervening door between the
adjacent levels, a smoke detector |
19 | | shall be installed on each level.
|
20 | | (c) Every structure which (1) contains more than one |
21 | | dwelling unit, or
(2) contains at least one dwelling unit and |
22 | | is a mixed-use structure, shall
contain at least one approved |
23 | | smoke detector at the uppermost ceiling of
each interior |
24 | | stairwell. The detector shall be installed on the ceiling,
at |
25 | | least 6 inches from the wall, or on a wall located between 4 |
|
| | HB0051 | - 6 - | LRB102 03963 CPF 13979 b |
|
|
1 | | and 6
inches from the ceiling.
|
2 | | (d) It shall be the responsibility of the owner of a |
3 | | structure to supply
and install all required detectors. The |
4 | | owner shall be responsible for
making reasonable efforts to |
5 | | test and maintain detectors in common
stairwells and hallways. |
6 | | It shall be the responsibility of a tenant to
test and to |
7 | | provide general maintenance for the detectors within the
|
8 | | tenant's dwelling unit or rooming unit, and to notify the |
9 | | owner or the
authorized agent of the owner in writing of any |
10 | | deficiencies which the
tenant cannot correct. The owner shall |
11 | | be responsible for providing one
tenant per dwelling unit with |
12 | | written information regarding detector
testing and |
13 | | maintenance.
|
14 | | The tenant shall be responsible for replacement of any |
15 | | required batteries
in the smoke detectors in the tenant's |
16 | | dwelling unit, except that the owner
shall ensure that such |
17 | | batteries are in operating condition at the time
the tenant |
18 | | takes possession of the dwelling unit. The tenant shall |
19 | | provide
the owner or the authorized agent of the owner with |
20 | | access to the dwelling
unit to correct any deficiencies in the |
21 | | smoke detector which have been
reported in writing to the |
22 | | owner or the authorized agent of the owner.
|
23 | | (e) The requirements of this Section shall apply to any |
24 | | dwelling unit
in existence on July 1, 1988, beginning on that |
25 | | date. Except as provided
in subsections (f) and (g), the smoke |
26 | | detectors required in such dwelling
units may be either: |
|
| | HB0051 | - 7 - | LRB102 03963 CPF 13979 b |
|
|
1 | | battery powered provided the battery is a self-contained, |
2 | | non-removable, long-term long term battery, or wired into the |
3 | | structure's AC power
line, and need not be interconnected.
|
4 | | (1) The battery requirements of this Section shall |
5 | | apply to battery-powered battery powered smoke detectors |
6 | | that: (A) are in existence and exceed 10 years from the |
7 | | date of their being manufactured; (B) fail fails to |
8 | | respond to operability tests or otherwise malfunction |
9 | | malfunctions ; or (C) are newly installed. |
10 | | (2) The battery requirements of this Section do not |
11 | | apply to: (A) a fire alarm, smoke detector, smoke alarm, |
12 | | or ancillary component that is electronically connected as |
13 | | a part of a centrally monitored or supervised alarm |
14 | | system; (B) a fire alarm, smoke detector, smoke alarm, or |
15 | | ancillary component that uses: (i) a low-power radio |
16 | | frequency wireless communication signal, or (ii) Wi-Fi or |
17 | | other wireless Local Area Networking capability to send |
18 | | and receive notifications to and from the Internet, such |
19 | | as early low battery warnings before the device reaches a |
20 | | critical low power level; or (C) such other devices as the |
21 | | State Fire Marshal shall designate through its regulatory |
22 | | process. |
23 | | (f) In the case of any dwelling unit that is newly |
24 | | constructed,
reconstructed, or substantially remodelled after |
25 | | December 31, 1987, the
requirements of this Section shall |
26 | | apply beginning on the first day of
occupancy of the dwelling |
|
| | HB0051 | - 8 - | LRB102 03963 CPF 13979 b |
|
|
1 | | unit after such construction, reconstruction or
substantial |
2 | | remodelling. The smoke detectors required in such dwelling
|
3 | | unit shall be permanently wired into the structure's AC power |
4 | | line, and if
more than one detector is required to be installed |
5 | | within the dwelling
unit, the detectors shall be wired so that |
6 | | the actuation of one detector
will actuate all the detectors |
7 | | in the dwelling unit.
|
8 | | In the case of any dwelling unit that is newly |
9 | | constructed,
reconstructed, or substantially remodeled on or |
10 | | after January 1, 2011, smoke detectors permanently wired into |
11 | | the structure's AC power line must also maintain an |
12 | | alternative back-up power source, which may be either a |
13 | | battery or batteries or an emergency generator. |
14 | | (g) Every hotel shall be equipped with operational |
15 | | portable
smoke-detecting alarm devices for the deaf and |
16 | | hearing impaired of audible
and visual design, available for |
17 | | units of occupancy.
|
18 | | Specialized smoke detectors smoke-detectors for the deaf |
19 | | and hearing impaired shall be
available upon request by guests |
20 | | in such hotels at a rate
of at least one such smoke detector |
21 | | per 75 occupancy units or portions
thereof, not to exceed 5 |
22 | | such smoke detectors per hotel.
Incorporation or connection |
23 | | into an existing interior alarm system, so as
to be capable of |
24 | | being activated by the system, may be utilized in lieu of
the |
25 | | portable alarms.
|
26 | | Operators of any hotel shall post conspicuously at the |
|
| | HB0051 | - 9 - | LRB102 03963 CPF 13979 b |
|
|
1 | | main desk a
permanent notice, in letters at least 3 inches in |
2 | | height, stating that
smoke detector alarm devices for the deaf |
3 | | and hearing impaired are
available. The proprietor may require |
4 | | a refundable deposit for a portable
smoke detector not to |
5 | | exceed the cost of the detector.
|
6 | | (g-5) A hotel, as defined in this Act, shall be |
7 | | responsible for installing and maintaining smoke detecting |
8 | | equipment. |
9 | | (h) Compliance with an applicable federal, State , or local |
10 | | law or
building code which requires the installation and |
11 | | maintenance of smoke
detectors in a manner different from this |
12 | | Section, but providing a level of
safety for occupants which |
13 | | is equal to or greater than that provided by
this Section, |
14 | | shall be deemed to be in compliance with this Section, and
the |
15 | | requirements of such more stringent law shall govern over the
|
16 | | requirements of this Section.
|
17 | | (i) (Blank). The requirements of this Section shall not |
18 | | apply to dwelling units and hotels within municipalities with |
19 | | a population over 1,000,000 inhabitants. |
20 | | (Source: P.A. 100-200, eff. 1-1-23; revised 8-19-20.)
|
21 | | Section 95. No acceleration or delay. Where this Act makes |
22 | | changes in a statute that is represented in this Act by text |
23 | | that is not yet or no longer in effect (for example, a Section |
24 | | represented by multiple versions), the use of that text does |
25 | | not accelerate or delay the taking effect of (i) the changes |